Summary: A complete guide to commercial kitchen exhaust systems covering system components, airflow calculation methods, grease filter selection, fan/duct design, installation standards, and environmental compliance requirements.

Commercial kitchen exhaust systems are critical infrastructure that directly impacts working conditions, food safety, and environmental compliance. Poor design leads to hot kitchens, grease backflow, excessive noise, and regulatory violations. This guide covers every aspect of exhaust system design from component selection to maintenance protocols.

1. System Components & Principles

A complete exhaust system consists of 6 core components:

Component Function Location
Stainless Steel Hood Capture cooking grease and heat Directly above cooking surface, 26–30 in high
Grease Filter / Precipitator Remove grease particles for emission compliance Upstream of fan or outdoors
Centrifugal Exhaust Fan Provide airflow动力, overcome duct resistance End of duct run or outdoors
Ductwork Transport grease-laden air to discharge Hood → filter → fan → discharge
Silencer Reduce fan operating noise Fan outlet end
Fire Damper (280°C) Auto-close on fire to block spread Wall/floor penetrations

2. Airflow Calculation Methods

Method 1: By Hood Area

Formula: Q = Hood Area (m²) × Face Velocity (m/s) × 3600

  • Chinese kitchen face velocity: 0.5–0.8 m/s
  • Western kitchen face velocity: 0.3–0.5 m/s
  • Example: 4m² hood, 0.6 m/s → Q = 4 × 0.6 × 3600 = 8,640 m³/h

Method 2: By Kitchen Area

Kitchen Type Air Changes/Hr Per m² Reference
Chinese kitchen (high-BTU wok) 50–60 ACH 100–120 m³/h per m²
Western kitchen 30–40 ACH 60–80 m³/h per m²
Cafeteria / fast food 40–50 ACH 80–100 m³/h per m²
Bakery / pastry 20–30 ACH 40–60 m³/h per m²

Makeup Air Calculation

Makeup air = Exhaust air × 80%. Maintains slight negative pressure (-5 to -10 Pa) to prevent grease migration into dining areas.

3. Grease Filter / Precipitator Selection

Type Efficiency Best For Price (USD) Pros / Cons
Electrostatic Precipitator 90–98% Mid-to-high-end restaurants $1,100–$4,200 High efficiency; monthly cleaning required
UV Photolysis 85–95% Odor-sensitive locations $700–$2,100 Removes odors; lamp replacement quarterly
Composite (ESP + UV) 95–99% Strict environmental zones $2,100–$7,000 Highest efficiency; highest investment
Mechanical Filter 60–80% Pre-treatment / auxiliary $280–$700 Low cost; moderate efficiency

Selection Guidelines

  • Capacity ≥ system exhaust volume (1.1–1.2x safety factor)
  • Efficiency ≥ 95% (urban centers recommend 98%+)
  • Service clearance: 20 in (500mm) before and after unit

4. Fan, Duct & Installation

Component Selection Criteria Price (USD)
Centrifugal Fan Match filter capacity, static pressure ≥800Pa $420–$1,700
Ductwork Galvanized or SS, sized for 8–12 m/s velocity $28–$70/ft
Silencer Impedance composite, 15–25 dB reduction $140–$560
Makeup Air Unit 80% of exhaust, filtered + heated $700–$2,100
Fire Damper (280°C) Thermal auto-close at fire-rated penetrations $70–$210

Maintenance Schedule

Item Frequency Action
Hood cleaning Weekly Clean filters and interior grease
Precipitator cleaning Monthly (1–2x) Clean collector plates, check insulators
Fan inspection Quarterly Check impeller balance, bearing lubrication
Duct inspection Semi-annually Check seals and grease accumulation
Fire damper test Quarterly Test auto-close function

5. FAQ

What are the system components?
Stainless steel hood, grease filter/precipitator, centrifugal exhaust fan, ductwork, silencer, and fire damper. The grease filter is the most critical component for emission compliance.
How to calculate exhaust airflow?
Q = Hood area × face velocity × 3600. Chinese kitchens: 0.5–0.8 m/s face velocity (100–120 m³/h per m²). Western kitchens: 0.3–0.5 m/s (60–80 m³/h per m²). Makeup air = exhaust × 80%.
How to select a grease filter?
Efficiency 95%+ (98%+ for urban areas). Choose electrostatic or composite (ESP+UV) type. Capacity ≥ exhaust volume × 1.1. Clean electrostatic units monthly for optimal performance.
How to reduce exhaust system noise?
1. Install silencer on fan outlet (15–25 dB reduction). 2. Mount fan outdoors or in mechanical room. 3. Flexible connections at wall penetrations. 4. Select low-noise centrifugal fans (≤65 dB). 5. Regular impeller balancing maintenance.
What is the exhaust system investment?
Small restaurant (320–540 sq ft kitchen): $2–5.5K. Medium (540–1,075 sq ft): $5.5–14K. Large kitchen (1,075+ sq ft): $14–42K. Includes hood, precipitator, fan, ductwork, and makeup air system.

6. About Fengzhida

Fengzhida is a professional commercial kitchen equipment manufacturer in Zhongshan, Guangdong, China, offering complete exhaust system solutions. OEM/ODM available. Learn more: Fengzhida Official Website.

Related: Kitchen Equipment List | Hotel Kitchen Setup | Seafood Kitchen

This article was originally published by Fengzhida Commercial Kitchen Equipment.

ShareCopy link to share on WeChat

Interested in Our Equipment?

Tell us about your kitchen requirements and we will provide tailored recommendations and pricing